6-34
Programming Your Application
590+ Series DC Digital Converter
DIGITAL OUTPUTS
This function block allows you to output digital parameters within the software to other
equipment.
A digital output can be configured to point
to any digital value within the software
system and output information depending
upon the status of that value.
Functional Description
Configurable Digital Outputs
INPUT
THRESHOLD
IP
OP
X
|X|
1
0
%
MODULUS
DIAGNOSTIC
INVERTED
Digout 1 (B5)
77
–
[ 97] INPUT
FALSE
–
[359] INVERTED
0.00 %
–
[195] THRESHOLD
TRUE
–
[ 43] MODULUS
DIGOUT 1 (B5)
[ 74]
–
OFF
Digout 3 (B7
125
–
[ 99] INPUT
FALSE
–
[361] INVERTED
0.00 %
–
[197] THRESHOLD
TRUE
–
[ 45] MODULUS
DIGOUT 3 (B7)
[ 76]
–
OFF
Digout 2 (B6)
122
–
[ 98] INPUT
FALSE
–
[360] INVERTED
0.00 %
–
[196] THRESHOLD
TRUE
–
[ 44] MODULUS
DIGOUT 2 (B6)
[ 75]
–
OFF
MMI Menu Map
1
SYSTEM
2
CONFIGURE I/O
3
DIGITAL OUTPUTS
4
DIGOUT 1 (B5)
4
DIGOUT 2 (B6)
4
DIGOUT 3 (B7)
THRESHOLD (>)
MODULUS
SOURCE TAG
INVERTED
Parameter
Tag
Range
INPUT
97, 98, 99
0 to 639
(SOURCE TAG)
Enter the tag number providing the source of the variable to control the digital output. Refer
to “Special Links”, page 6-1.
INVERTED
359, 360, 361
FALSE / TRUE
Selects to invert the output when TRUE.
THRESHOLD
195, 196, 197
-300.00 to 300.00 %
(THRESHOLD (>))
The threshold which the input value must exceed to set the output to TRUE.
MODULUS
43, 44, 45
FALSE / TRUE
When TRUE, the absolute value of the source value is used for the threshold test.
DIGOUT 1 (B5) to
DIGOUT 3 (B7)
74, 75, 76
OFF / ON
Refer to the DIAGNOSTICS function block description, page 6-23.