Technical Specifications
11-1
590+ Series DC Digital Converter
1
1
T
ECHNICAL
S
PECIFICATIONS
Environmental Details
Operating Temperature
Frame 1 :
0
q
C to +45
q
C
Frame 2 :
0
q
C to +45
q
C
Frame 3 :
0
q
C to +45
q
C
Frame 4 :
0
q
C to +40
q
C
Frame 5 :
0
q
C to +40
q
C
Frame H :
0
q
C to +40
q
C
Operating temperature is defined as the ambient temperature to the immediate surround of the
Converter, when the Converter and other equipment adjacent to it is operating at worst case
conditions.
Output current values should be derated at 1% per degree Centigrade above rated temperature
up to a maximum of 55°C.
Storage Temperature
-25
q
C to +55
q
C
Shipping Temperature
-25
q
C to +70
q
C
Product Enclosure Rating
IP00 (Europe) [Frame 1 unit is IP20]
UL Open Type (North America/Canada)
If the product enclosure is totally enclosed, the exposed metal surface dissipates approximately
50W/m² for a 10°C temperature rise of internal air above ambient.
Vibration
Test Fc of EN60068-2-6
10Hz<=f<=57Hz sinusoidal 0.075mm amplitude
57Hz<=f<=150Hz sinusoidal 1g
10 sweep cycles per axis on each of three mutually perpendicular axis
Altitude
If >500 metres (1650 feet) above sea level, derate Motor Power rating by 1% per 200 metres
(660 feet) to a maximum of 5,000 metres (16,500 feet)
Humidity
Maximum 85% relative humidity at 40
q
C non-condensing
Atmosphere
Non flammable, non corrosive and dust free
Climatic Conditions
Class 3k3, as defined by EN60721-3-3 (1995)
Safety
Europe
EN50178 (1998), when fitted inside a cubicle
North America/Canada
UL508C
Overvoltage Category
Overvoltage Category III (3-phase supply), Overvoltage Category II (auxiliary supply)
Pollution Degree
Pollution Degree 2
EMC Compliance
All models
European Community Directive 89/336/EEC
All models
EN61800-3 (1997) Table 11 : conducted emissions when installed in accordance with the
instructions in Chapter 3. Refer to "Mounting the Converter".
EN61800-3 (1997) Immunity requirements
EN61800-3 (1997) Table 12 Radiated emissions
If fitted with specified
external filters
(except Frame H)
EN61800-3 (1997) restricted distribution: conducted emissions