HPM6 Power Management Controller User Manual
Page 86 of
146
No.
Items
Range
Default
Description
95.
Return Value
(0-200.0)%
149.0
96.
Delay Value
(0.1-3600.0)s 10.0
97.
Alarm Type
(0-6)
2: Trip
98.
Active Range
(0-20)
0: Always
Active
99.
Gen Current
5 Set
Action
(0-1)
0: Disable
Inverse time overcurrent. The
larger the over current, the less
the time. The formulation is:
T=t/((IA/IT)-1)
2
T: Overload current delay value
(s)
t: Timing multiplier rate
IA: Current load max current
(L1/L2/L3)
IT: Overload current set value
For example:
t=36.0
IA=550A
IT=500A
Then T=3600s (1h)
100.
Auto ACK
(0-1)
0: Disable
101.
Alarm Self-lock
(0-1)
0: Disable
102.
Threshold
(0-200.0)%
120.0
103.
Return Value
(0-200.0)%
119.0
104.
Delay Value
(0.1-36.0)s
12.0
105.
Alarm Type
(0-6)
1: Warning
106.
Active Range
(0-20)
0: Always
Active
107.
Gen Current
6 Set
Action
(0-1)
0: Disable
108.
Auto ACK
(0-1)
0: Disable
109.
Alarm Self-lock
(0-1)
0: Disable
110.
Threshold
(0-200.0)%
140.0
111.
Return Value
(0-200.0)%
139.0
112.
Delay Value
(0.1-36.0)s
36.0
113.
Alarm Type
(0-6)
2: Trip
114.
Active Range
(0-20)
0: Always
Active
115.
Unbalanced
Current 1 Set
Action
(0-1)
1: Enable
3P3W
Two-meter
method
enable
When
controller
detects
unbalanced current is greater
than set value, it will initiate
alarm
signal
and
alarm
information will be displayed
on LCD.
116.
Auto ACK
(0-1)
0: Disable
117.
Alarm Self-lock
(0-1)
0: Disable
118.
Threshold
(0-200.0)%
20.0
119.
Return Value
(0-200.0)%
19.0
120.
Delay Value
(0.1-3600.0)s 5.0
121.
Alarm Type
(0-6)
1: Warning
122.
Active Range
(0-20)
3: After Gen
Close
123.
Unbalanced
Current 2 Set
Action
(0-1)
0: Disable
124.
Auto ACK
(0-1)
0: Disable
125.
Alarm Self-lock
(0-1)
0: Disable
126.
Threshold
(0-200.0)%
20.0
127.
Return Value
(0-200.0)%
19.0
128.
Delay Value
(0.1-3600.0)s 5.0
129.
Alarm Type
(0-6)
1: Warning
130.
Active Range
(0-20)
3: After Gen
Close
131.
Over Power 1 Action
(0-1)
1: Enable
When controller detects power