HPM6 Power Management Controller User Manual
Page 102 of
146
No.
Name
Description
Auto
Mode
Semi-auto
Mode
Manual
Mode
2: Before Gen Close
3: After Gen Close
4: Gen Close on Bus
5: No Gen Close on Bus
6: Gen Normal
7: Other Gens Close
8: Start Delay
9: After Gen Close Delay
10: Before Gen Close Delay
11: Gen Load Normal
12: Gen Close Delay on Bus
13: No Gen Close Delay on Bus
14: Gen Normal Delay
15: Other Gens Close Delay
16: Gen Load Normal Delay
17: Reserved
18: Reserved
19: Reserved
20: Reserved
Input ports names can be downloaded into
controller after defined using PC software.
2.
Close Input
Switch close feedback signal input, used
for indicating switch close/open status.
If this signal no corresponding response in
c/o, controller will initiate feedback fault
alarm.
There must be one and only one input port
to select this function, otherwise controller
will initiate feedback fault alarm.
√
√
√
3.
Open Input
Switch open feedback signal input,
opposite the close feedback signal.
After it is configured for input port, switch
status must be indicated with close input
and open input. If two signals are not
matched or signal is not correct in c/o,
controller will initiate feedback fault alarm.
√
√
√
4.
Speed Raise
Speed raise relay is active when the input is
active.
Х
Х
√
5.
Speed Drop
Speed drop relay is active when the input is
active.
Х
Х
√
6.
Volt Raise
Voltage raise relay is active when the input Х
Х
√