HPM6 Power Management Controller User Manual
Page 90 of
146
No.
Items
Range
Default
Description
239.
Chinese Character
String
NEL1
Character string only can be
set via upper computer.
240.
English Character
String
NEL1
241.
NEL2
Trip
Auto ACK
(0-1)
0: Disable
242.
Alarm Self-lock
(0-1)
0: Disable
243.
Alarm Type
(0-6)
1: Warning
244.
Active Range
(0-20)
0: Always
Active
245.
Power Trip
Action
(0-1)
1: Enable
When any bus genset current
is greater than set value,
external non-essential load 2
will trip.
246.
Threshold (0-200.0)%
100.0
247.
Return
Value
(0-200.0)%
99.0
248.
Delay
Value
(0.1-3600.0)s 8.0
249.
Current
Trip
Action
(0-1)
0: Disable
When any bus genset current
is greater than set value,
external non-essential load 2
will trip.
250.
Threshold (0-200.0)%
100.0
251.
Return
Value
(0-200.0)%
99.0
252.
Delay
Value
(0.1-3600.0)s 8.0
253.
Chinese Character
String
NEL2
Character string only can be
set via upper computer.
254.
English Character
String
NEL2
255.
NEL 3
Trip
Auto ACK
(0-1)
0: Disable
256.
Alarm Self-lock
(0-1)
0: Disable
257.
Alarm Type
(0-6)
1: Warning
258.
Active Range
(0-20)
0: Always
Active
259.
Power Trip
Action
(0-1)
1: Enable
When any bus genset current
is greater than set value,
external non-essential load 3
will trip.
260.
Threshold (0-200.0)%
100.0
261.
Return
Value
(0-200.0)%
99.0
262.
Delay
Value
(0.1-3600.0)s 10.0
263.
Current
Trip
Action
(0-1)
0: Disable
When any bus genset current
is greater than set value,
external non-essential load 3
will trip.
264.
Threshold (0-200.0)%
100.0
265.
Return
Value
(0-200.0)%
99.0
266.
Delay
Value
(0.1-3600.0)s 10.0