HPM6 Power Management Controller User Manual
Page 75 of
146
No.
Items
Range
Default
Description
36
SHIFT 2
Auto ACK
(0-1)
0: Disable
37
Alarm
Self-lock
(0-1)
0: Disable
38
Threshold (0-60.0)°
6.0
39
Return
Value
(0-60.0)°
5.0
40
Delay Value (0.1-3600.0)s
0.1
41
Alarm Type (0-6)
1: Warning
42
Active
Range
(0-20)
6:
Gen
Normal
43
Voltage
THD 1 Set
Action
(0-1)
0: Disable
When controller detects voltage
total
harmonic
distortion
percentage is greater than set
value, it will initiate alarm signal
and alarm information will be
displayed on LCD.
44
Auto ACK
(0-1)
0: Disable
45
Alarm
Self-lock
(0-1)
0: Disable
46
Threshold (0-200.0)%
10.0
47
Return
Value
(0-200.0)%
5.0
48
Delay Value (0.1-3600.0)s
5.0
49
Alarm Type (0-6)
1: Warning
50
Active
Range
(0-20)
6:
Gen
Normal
51
Voltage
THD 2 Set
Action
(0-1)
0: Disable
52
Auto ACK
(0-1)
0: Disable
53
Alarm
Self-lock
(0-1)
0: Disable
54
Threshold (0-200.0)%
10.0
55
Return
Value
(0-200.0)%
5.0
56
Delay Value (0.1-3600.0)s
5.0
57
Alarm Type (0-6)
1: Warning
58
Active
Range
(0-20)
6:
Gen
Normal
59
Voltage
SHD 1 Set
Action
(0-1)
0: Disable
When controller detects voltage
any one harmonic distortion
percentage is greater than set
value, it will initiate alarm signal
and alarm information will be
displayed on LCD.
60
Auto ACK
(0-1)
0: Disable
61
Alarm
Self-lock
(0-1)
0: Disable
62
Threshold (0-200.0)%
10.0
63
Return
Value
(0-200.0)%
5.0
64
Delay Value (0.1-3600.0)s
5.0
65
Alarm Type (0-6)
1: Warning
66
Active
(0-20)
6:
Gen