HPM6 Power Management Controller User Manual
Page 129 of
146
No.
Item
Range
Default
Description
Limit
11
Active Distribution
Weight
(0.0-200.0)% 100.0
The weight of power distribution. For
example, when the active distribution weight
is 50%, the current genset shares load
according to 50% of rated power.
12
Reactive
Distribution Weight
(0.0-200.0)% 100.0
13
Freq.
Droop
Enable
(0-1)
0
When it is enabled, target frequency adjusts
according to active load.
14
No-load (0.0-200.0)% 101.0
15
Full-load (0.0-200.0)% 100.0
16
Volt
Droop
Enable
(0-1)
0
When it is enabled, target voltage adjusts
according to reactive load.
17
No-load (0.0-200.0)% 101.0
18
Full-load (0.0-200.0)% 100.0
19
Dead Bus Voltage
(1.0-20.0)%
10.0
Bus is unavailable when bus voltage is below
the dead bus voltage.
20
Sync. Voltage
Difference
(1.0-10.0)%
5.0
Voltage synchronization is considered when
voltage difference percentage of gen and bus
is lower than sync voltage difference.
21
Sync. Positive Freq
Difference
(0-2.00)Hz
0.20
Frequency synchronization is considered
when frequency difference of gen and bus is
lower than sync positive frequency difference
and greater than sync. negative frequency
difference.
22
Sync. Negative
Freq Difference
(0-2.00)Hz
0.10
23
Sync. Phase
Difference
(0-20)°
10
Phase synchronization is considered when
the initial phase difference of gen and bus is
lower than sync phase difference.
24
Phase
Compensation
(0-360.0)°
0.0
Phase difference compensation of gen and
bus sampling.
25
Sync. Failure Time
(5.0-300.0)s
60.0
When synchronization signal is not detected
within set sync. failure time, corresponding
alarm will be initiated according to action
type.
26
Sync. Failure
Action
(0-6)
1
0: Block; 1: Warning; 2: Trip; 3: Trip and Stop;
4: Safety Trip; 5: Safety Trip and Stop; 6:
Indication.
27
Start Options
(0-2)
0
0: Linear Start; 1: Duty Time Start.
28
Active Output
Mode
(0-2)
0
0 Share Power Output
1 Fixed Power Output
2 Analog Control Output
29
Reactive Output
Mode
(0-2)
0
0 Share Power Output
1 Fixed Power Output
2 Analog Control Output
30
Reserved Running
Gensets
(1-16)
1
The minimum load running gensets on the
bus.