HPM6 Power Management Controller User Manual
Page 127 of
146
No.
Name
Description
6
Reserved
7
Gen Voltage
8
Gen Frequency
9
Gen Active Power
10
Gen Reactive Power
11
Gen Apparent Power
12
Gen Power Factor
13
Gen A Phase Current
14
Gen B Phase Current
15
Gen C Phase Current
16
Gen Max. Current
17
Bus Left Power
18
Gen Left Power
19
Reserved
20
PLC Variant X1
21
PLC Variant X2
22
PLC Variant X3
23
PLC Variant X4
24
PLC Variant X5
25
PLC Variant X6
26
Reserved
27
Reserved
28
Reserved
29
Reserved
30
Reserved
12.10
GB SETTING
Table 40 – GB Settings
No.
Item
Range
Default
Description
GB Setting
1
Close Delay
(0-20.0)s
3.0
Close pulse width, it is continuous
output when set to 0.
2
Open Delay
(0-20.0)s
3.0
Open pulse width, it is continuous
output when set to 0.
3
Action Time
(0-2000)ms
100
Time for switch receives close signal to
contact closes.
4
Storage Time
(0-3000)ms
100
Coil storage time before actions.
5
Semi-auto
Intelligent
Open
(0-1)
1
0: Disable; 1: Enable.
When it is enabled, in semi-auto mode, it
intelligently judges whether to open.
6
Failure
Enable
(0-1)
1: Enable
There is no corresponding signal for