HPM6 Power Management Controller User Manual
Page 84 of
146
No.
Items
Range
Default
Description
59.
Current SHD
2 Set
Action
(0-1)
0: Disable
60.
Auto ACK
(0-1)
0: Disable
61.
Alarm Self-lock
(0-1)
0: Disable
62.
Threshold
(0-200.0)%
10.0
63.
Return Value
(0-200.0)%
5.0
64.
Delay Value
(0.1-3600.0)s 5.0
65.
Alarm Type
(0-6)
1: Warning
66.
Active Range
(0-20)
3: After Gen
Close
67.
Gen Current
1 Set
Action
(0-1)
1: Enable
Set value is percentage of gen
rated full-load current, return
value and delay value can be
set
according
to
actual
situation.
68.
Auto ACK
(0-1)
0: Disable
69.
Alarm Self-lock
(0-1)
0: Disable
70.
Threshold
(0-200.0)%
100.0
71.
Return Value
(0-200.0)%
99.0
72.
Delay Value
(0.1-3600.0)s 20.0
73.
Alarm Type
(0-6)
0: Block
1: Warning
2: Trip
3: Trip and
Stop
4: Safety Trip
5: Safety Trip
and Stop
6: Indication
1: Warning
74.
Active Range
(0-20)
0: Always
Active
1: Inactive
2: Before Gen
Close
3: After Gen
Close
4: Gen Close
on Bus
5: No Gen
Close on Bus
6: Gen Normal
7: Other Gens
Close
8: Start Delay
9: After Gen
0: Always
Active