HPM6 Power Management Controller User Manual
Page 77 of
146
No.
Items
Range
Default
Description
5: No Gen Close
on Bus
6: Gen Normal
7:
Other
Gens
Close
8: Start Delay
9: After Gen Close
Delay
10: Before Gen
Close Delay
11:
Gen
Load
Normal
12: Gen Close
Delay on Bus
13: No Gen Close
Delay on Bus
14: Gen Normal
Delay
15: Other Gens
Close Delay
16:
Gen
Load
Normal Delay
17-20: Reserved
83
Over
Voltage 2
Set
Action
(0-1)
1: Enable
84
Auto ACK
(0-1)
0: Disable
85
Alarm
Self-lock
(0-1)
0: Disable
86
Threshold (0-200.0)%
115.0
87
Return
Value
(0-200.0)%
114.0
88
Delay Value (0.1-3600.0)s
1.0
89
Alarm Type (0-6)
2: Trip
90
Active
Range
(0-20)
0:
Always
Active
91
Over
Voltage 3
Set
Action
(0-1)
0: Disable
92
Auto ACK
(0-1)
0: Disable
93
Alarm
Self-lock
(0-1)
0: Disable
94
Threshold (0-200.0)%
120.0
95
Return
Value
(0-200.0)%
119.0
96
Delay Value (0.1-3600.0)s
1.0