HPM6 Power Management Controller User Manual
Page 133 of
146
No.
Item
Range
Default
Description
Pulse
before parallel connection.
22
Gain
(0-30000)%
10
23
Dead Band
(0-10.0)%
1.0
Phase Sync
24
Phase Stable Time
(0-20.0)s
2.0
It
will
close
after
phase
synchronization and delay set value
in static synchronization.
25
Analog
Control
Gain
(0-2000)%
20
The internal analog is adjusted to
control the generator phase before
parallel connection.
26
Stability
(0-2000)%
20
27
Change
(0-2000)%
0
28
Relay
Control
Period
(100-10000)ms 2000
The internal relay is adjusted to
control the generator phase before
parallel connection.
29
Min Adjust
Pulse
(10-1600)ms
100
30
Gain
(0-30000)%
10
31
Dead Band
(0-10.0)%
1.0
Active Power Control
32
Voltage
Control
Gain
(0-2000)%
20
The internal analog voltage is
adjusted to control active power
after parallel connection.
33
Stability
(0-2000)%
20
34
Change
(0-2000)%
0
35
Relay
Control
Period
(100-10000)ms 2000
The internal relay is adjusted to
control active power after parallel
connection.
36
Min, Adjust
Pulse
(10-1600)ms
100
37
Gain
(0-30000)%
10
38
Dead Band
(0-10.0)%
1.0
Reactive Power Control
39
Voltage
Control
Gain
(0-2000)%
20
The internal analog voltage is
adjusted to control reactive power
after parallel connection.
40
Stability
(0-2000)%
20
41
Change
(0-2000)%
0
42
Relay
Control
Period
(100-10000)ms 2000
The internal relay is adjusted to
control reactive power after parallel
connection.
43
Min. Adjust
Pulse
(10-1600)ms
100
44
Gain
(0-30000)%
10
45
Dead Band
(0-10.0)%
1.0
46
Min. Load Percentage
(0-100.0)%
10.0
The active power percentage of the
unit from soft unloaded to the
opening.
47
Fixed Active Power%
(0-100.0)%
30.0
The percentage of active power
output in fixed power mode.
48
Fixed Reactive Power Mode (0-1)
0
0: Power Percentage; 1: Power
Factor
49
Fixed Reactive Power%
(0-100.0)%
8.0
The percentage of reactive power
output in fixed power mode.