HPM6 Power Management Controller User Manual
Page 46 of
146
10.3.7
TS #8, TS #9, TS #10 GEN/BUS VOLTAGE, GEN/EARTH CURRENT INPUT PORT
Table 24 – TS #8, TS #9, TS #10 Gen/Bus Voltage, Gen/Earth Current Input Port
Terminal
Function
Cable Size
Description
Remark
72
L1 (Bus)
1.5mm
2
(Bus) A phase voltage input
73
L2 (Bus)
1.5mm
2
(Bus) B phase voltage input
74
L3 (Bus)
1.5mm
2
(Bus) C phase voltage input
75
N (Bus)
1.5mm
2
(Bus) N phase voltage input
76
L1 (Gen)
1.5mm
2
(Gen) A phase voltage input
77
L2 (Gen)
1.5mm
2
(Gen) B phase voltage input
78
L3 (Gen)
1.5mm
2
(Gen) C phase voltage input
79
N (Gen)
1.5mm
2
(Gen) N phase voltage input
80
S1 (CT1)
2.5mm
2
Gen A phase current
Rated input 5A
81
S2 (CT1)
2.5mm
2
82
S1 (CT2)
2.5mm
2
Gen B phase current
Rated input 5A
83
S2 (CT2)
2.5mm
2
84
S1 (CT3)
2.5mm
2
Gen C phase current
Rated input 5A
85
S2 (CT3)
2.5mm
2
86
S1 (CT4)
2.5mm
2
Earth current
Rated input 5A
87
S2 (CT4)
2.5mm
2
10.3.8
COMMUNICATION PORT
Table 25 – Communication Port
Terminal
Function
Cable Size
Parameter
Remark
USB DEVICE
USB
communication
port
USB-TYPE B port, connect PC
software.
USB HOST
USB port
USB-TYPE A port, connect USB to
record historical data.
ETHERNET 1
SF/UTP
CAT5e
ETHERNET port 1
RJ45 port, connect master control
module, PC software, display module
or other monitoring platforms.
ETHERNET 2
SF/UTP
CAT5e
ETHERNET port 2
ETHERNET 3
SF/UTP
CAT5e
ETHERNET port 3
ETHERNET 4
SF/UTP
CAT5e
ETHERNET port 4