HPM6 Power Management Controller User Manual
Page 132 of
146
12.12
SYNCHRONOUS CALIBRATION
Table 42 – Synchronous Calibration List
No.
Item
Range
Default
Description
Synchronous Calibration
1
Multi-set Comm. No.
(1-16)
2
Genset numbers on the network
bus.
2
Comm. Alarm Action
(0-6)
1
Communication alarm action when
the module on the network bus is
less
than
set
multi-set
communication numbers.
3
Module ID
(0-15)
1
ID in the communication network.
The ID should be unique throughout
the whole communication network.
4
Priority
(0-15)
1
The smaller of the number, the
higher of the priority.
5
GOV SW1
(0-20.00)
0
Default central current is 0mA.
6
GOV SW2
(0-20.00)
2.00
Default
current
range
is
(-3.0~+3.0)mA.
7
AVR SW1
(0-20.00)
0
Default central current is 0mA.
8
AVR SW2
(0-20.00)
2.00
Default
current
range
is
(-3.0~+3.0)mA.
Frequency Sync
9
Frequency Difference
(0-1.00)Hz
0.10
Adjusting generator frequency to
make it greater than the difference
value of bus frequency, that is the
sliding frequency difference of
dynamic sync.
10
Analog
Control
Gain
(0-2000)%
20
The internal analog is adjusted to
control the engine speed before
parallel connection.
11
Stability
(0-2000)%
20
12
Change
(0-2000)%
0
13
Relay
Control
Period
(100-10000)ms 2000
The internal relay is adjusted to
control the engine speed before
parallel connection.
14
Min Adjust
Pulse
(10-1600)ms
100
15
Gain
(0-30000)%
10
16
Dead Band
(0-10.0)%
1.0
Voltage Sync
17
Analog
Control
Gain
(0-2000)%
20
The internal analog is adjusted to
control the generator voltage
before parallel connection.
18
Stability
(0-2000)%
20
19
Change
(0-2000)%
0
20
Relay
Control
Period
(100-10000)ms 2000
The internal relay is adjusted to
control the generator voltage
21
Min Adjust (10-1600)ms
100