HPM6 Power Management Controller User Manual
Page 128 of
146
No.
Item
Range
Default
Description
7
Setting
Auto ACK (0-1)
0: Disable
close/open feedback input port in
switch close/open, and the alarm action
for no corresponding signal inputs for
other feedback signals (like current).
8
Alarm
Self-lock
(0-1)
1: Enable
9
Action
(0-6)
0: Block
10
Feedback
Fault
Setting
Enable
(0-1)
1: Enable
Action in close/open feedback and
switch real status are inconsistent.
11
Auto ACK (0-1)
0: Disable
12
Alarm
Self-lock
(0-1)
0: Disable
13
Action
(0-6)
1: Warning
14
Solenoid Valve Close
Time
(0-20.0)s
5.0
Close pulse width, it is continuous
output when set to 0.
15
Solenoid Valve Open
Time
(0-20.0)s
5.0
Open pulse width, it is continuous
output when set to 0.
NOTE:
If close feedback input port can’t be detected when close command is sent and after close delay, controller
will initiate close failure alarm. If there are other close signals (like there is current) besides close input por, controller will
initiate close feedback fault. If open feedback input port can’t be detected when open command is sent and after open
delay, controller will initiate open failure alarm. If there are other open signals (like no current) besides close input por,
controller will initiate open feedback fault.
12.11
SYNCHRONIZATION SETTING
Table 41 – Synchronization Settings
No.
Item
Range
Default
Description
Synchronization Setting
1
GOV Output
(0-2)
1
0: Internal relay; 1: Internal analog; 2: None.
2
GOV Reverse
Output Enable
(0-1)
0
0: Disable; 1: Enable.
3
GOV Loading
Action
(0-2)
1
0: None; 1: Adjust rated frequency; 2: Adjust
center point.
4
AVR Output
(0-2)
1
0: Internal relay; 1: Internal analog; 2: None.
5
AVR Reverse
Output Enable
(0-1)
0
0: Disable; 1: Enable.
6
AVR Loading
Action
(0-2)
1
0: None; 1: Adjust rated voltage; 2: Adjust
center point.
7
Load (P) Feedback
Coefficient
(0-100)%
50
The proportion of load frequency adjustment
PID coefficient in whole load active
adjustment coefficient.
8
Load (Q) Feedback
Coefficient
(0-100)%
50
The proportion of load voltage adjustment
PID coefficient in whole load reactive
adjustment coefficient.
9
Active Adjust. Limit (0-50.0)%
30.0
The max adjustment deviation of current
power from the target power value.
10
Reactive Adjust.
(0-50.0)%
30.0