HPM6 Power Management Controller User Manual
Page 88 of
146
No.
Items
Range
Default
Description
170.
Active Range
(0-20)
16: Gen Load
Normal Delay
171.
Low Power
Factor 2
Alarm Set
Action
(0-1)
1: Enable
172.
Auto ACK
(0-1)
0: Disable
173.
Alarm Self-lock
(0-1)
0: Disable
174.
Threshold
(0-200.0)%
0.70
175.
Return Value
(0-200.0)%
0.75
176.
Delay Value
(0.1-3600.0)s 5.0
177.
Alarm Type
(0-6)
1: Warning
178.
Active Range
(0-20)
16: Gen Load
Normal Delay
179.
Loss of
Excitation 1
Alarm Set
Action
(0-1)
1: Enable
When controller detects the
absolute value of reactive
power is greater than set value,
it will initiate alarm signal and
alarm information will be
displayed on LCD.
180.
Auto ACK
(0-1)
0: Disable
181.
Alarm Self-lock
(0-1)
0: Disable
182.
Threshold
(0-200.0)%
20.0
183.
Return Value
(0-200.0)%
19.0
184.
Delay Value
(0.1-3600.0)s 10.0
185.
Alarm Type
(0-6)
1: Warning
186.
Active Range
(0-20)
0: Always
Active
187.
Loss of
Excitation 2
Alarm Set
Action
(0-1)
1: Enable
188.
Auto ACK
(0-1)
0: Disable
189.
Alarm Self-lock
(0-1)
0: Disable
190.
Threshold
(0-200.0)%
20.0
191.
Return Value
(0-200.0)%
19.0
192.
Delay Value
(0.1-3600.0)s 10.0
193.
Alarm Type
(0-6)
1: Warning
194.
Active Range
(0-20)
0: Always
Active
195.
Active
Distribution
Imbalance 1
Action
(0-1)
1: Enable
Action for active distribution
percentage is greater that set
value.
196.
Auto ACK
(0-1)
0: Disable
197.
Alarm Self-lock
(0-1)
0: Disable
198.
Threshold
(0-200.0)%
20.0
199.
Return Value
(0-200.0)%
18.0
200.
Delay Value
(0.1-3600.0)s 60.0
201.
Alarm Type
(0-6)
1: Warning
202.
Active Range
(0-20)
3: After Gen
Close
203.
Active
Distribution
Imbalance 2
Action
(0-1)
0: Disable
1: Enable
0: Disable
204.
Auto ACK
(0-1)
0: Disable