HPM6 Power Management Controller User Manual
Page 113 of
146
Table 36 – Output Ports Function
No.
Name
Description
Remark
0.
Not Used
This port is invalid.
1.
Speed Raise
Active when the generator is raising speed.
2.
Speed Drop
Active when the generator is dropping speed.
3.
Volt Raise
Active when the generator is raising voltage.
4.
Volt Drop
Active when the generator is dropping voltage.
5.
Close Gen
Active when the close generator requirements
are reached.
6.
Open Gen
Active when the open generator requirements
are reached.
7.
Crank Output
Active when unit starts.
8.
Stop Output
Active when stopping.
9.
Remote Control
System
can
control
its
status
via
communication.
10.
Generator OK
Active when the rated voltage and rated
frequency are reached.
11.
Common Alarm
Active when genset alarm occurs.
12.
Common Indication Alarm Active when genset indication alarm occurs.
13.
Common Warning Alarm
Active when genset warning alarm occurs.
14.
Common Block Alarm
Active when genset block alarm occurs.
15.
Common Safety Trip
Alarm
Active when genset safety trip alarm occurs.
16.
Common Safety Trip and
Stop Alarm
Active when genset safety trip and stop alarm
occurs.
17.
Common Trip Alarm
Active when genset trips alarm occurs.
18.
Common Trip and Stop
Alarm
Active when genset trip and stop alarm occurs.
19.
Input 1 Active
Active when input port 1 is active.
20.
Input 2 Active
Active when input port 2 is active.
21.
Input 3 Active
Active when input port 3 is active.
22.
Input 4 Active
Active when input port 4 is active.
23.
Input 5 Active
Active when input port 5 is active.
24.
Input 6 Active
Active when input port 6 is active.
25.
Input 7 Active
Active when input port 7 is active.
26.
Input 8 Active
Active when input port 8 is active.
27.
Input 9 Active
Active when input port 9 is active.
28.
Input 10 Active
Active when input port 10 is active.
29.
Input 11 Active
Active when input port 11 is active.
30.
Input 12 Active
Active when input port 12 is active.
31.
Input 13 Active
Active when input port 13 is active.
32.
Input 14 Active
Active when input port 14 is active.