HPM6 Power Management Controller User Manual
Page 117 of
146
No.
Name
Description
Remark
124.
DG Insufficient Capacity
When the controller operates in SG mode and
load receiving mode, if DG on-load is active, but
DG capacity is insufficient to receive the full
load, it outputs.
125.
SG & DG Parallel No.
Exceeds Limit
When SG and DG are on-grid at the same time
or to be synchronized, the DG switch number
exceeds the set value, it outputs.
126.
Bus
Freq.
Change
Abnormal
Output when the bus frequency change rate
exceeds the set value and the delay value.
127.
Gen. Freq. Change
Abnormal
Generating frequency change rate exceeds the
set value and the delay value.
128.
Blackout
The controller outputs when it detects that the
whole ship is black out.
129.
NEL 1 Pre-tripping
Output when controller detects power, current
is greater than NEL trip set value and in delay.
130.
NEL 2 Pre-tripping
131.
NEL 3 Pre-tripping
132.
1# DIN16 IN1 Active
Outputs when DIN16-1 module input is active.
133.
1# DIN16 IN2 Active
134.
1# DIN16 IN3 Active
135.
1# DIN16 IN4 Active
136.
1# DIN16 IN5 Active
137.
1# DIN16 IN6 Active
138.
1# DIN16 IN7 Active
139.
1# DIN16 IN8 Active
140.
1# DIN16 IN9 Active
141.
1# DIN16 IN10 Active
142.
1# DIN16 IN11 Active
143.
1# DIN16 IN12 Active
144.
1# DIN16 IN13 Active
145.
1# DIN16 IN14 Active
146.
1# DIN16 IN15 Active
147.
1# DIN16 IN16 Active
148.
2# DIN16 IN1 Active
Outputs when DIN16-2 module input is active.
149.
2# DIN16 IN2 Active
150.
2# DIN16 IN3 Active
151.
2# DIN16 IN4 Active
152.
2# DIN16 IN5 Active
153.
2# DIN16 IN6 Active
154.
2# DIN16 IN7 Active
155.
2# DIN16 IN8 Active
156.
2# DIN16 IN9 Active
157.
2# DIN16 IN10 Active