HPM6 Power Management Controller User Manual
Page 36 of
146
No.
Types
Description
Alarm Type
24
HC3
Request
Failure
Warn
After heavy consumer
is active.
25
HC4
Request
Failure
Warn
After heavy consumer
is active.
Switch Protection
1
Fail to Close
When controller detects that there is no
Close
signal after the Close delay has expired, and no
other close signals (current, power), it will initiate a
block alarm.
Block
It is active after gen has
closed.
2
Fail to Open
When controller detects that there is no
Open
signal after the Open delay has expired, and no
other open signals (current, power), it will initiate a
block alarm.
Block
It is active after gen has
opened.
3
Close Fault
When controller detects that there is no
Close
signal after the Close delay has expired, but
detects other close signals (current, power), it will
initiate a warning alarm.
Warn
Always active.
4
Open Fault
When controller detects that there is no
Open
signal after the Open delay has expired, but
detects other open signals (current, power), it will
initiate a warning alarm.
Warn
Always active.
5
Unload Failure
When controller detects unload failure in set time,
it will initiate a warning alarm.
Warn
It is active in unloading.
6
Bustie Switch 0
Fault
The bustie switch fault signal of ring bus. When
controller detects fault signal (signal is
inconsistent), it will initiate an alarm.
Disabled
7
Bustie Switch 1
Fault
When controller detects bustie switch fault signal
(signal is inconsistent), it will initiate an alarm.
Warn
Always active.
8
Bustie Switch 2
Fault
Disabled
9
Bustie Switch 3
Fault
Disabled
10
Bustie Switch 4
Fault
Disabled
11
Bustie Switch 5
Fault
Disabled
12
Bustie
Series
Switch 0 Fault
Series switch refers to middle switch of bus
section has two or more isolating switches. When
Disabled