HPM6 Power Management Controller User Manual
Page 23 of
146
the genset stops completely and enters into standby state.
Table 7 – System Modes Description
Mode
Start/Stop Method
Close/Open
GOV/AVR
Alarm
Protection
Description
Manual
Exterior (not via
controller)
Exterior (not via
controller)
Exterior
(not
via
controller)
Auto
Also
called
switchboard
mode, mainly
for monitoring
and protection.
Semi-auto
Exterior
(by
controller)
Exterior
(by
controller)
Auto
Auto
Used
for
semi-auto
power station.
Auto
Auto
Auto
Auto
Auto
Used
for
full-auto power
station.
7.2
START MODE DESCRIPTION
Table 8 – Start Mode Description
Start Mode
Start Method
Stop Method
Auto
Mode
Semi-auto
Mode
Manual
Mode
Linear Start
Mode
Start
the
gensets
according to the set
priority. The genset with
higher priority will start
first. The smaller the
number, the higher the
priority.
Stop
the
gensets
according
to
the
priority, genset with
lower priority will stop
first.
E.g. If start sequence is
1-2-3, then the stop
sequence of 3-2-1.
√
Х
Х
Duty Time
Start Mode
The gensets which has
the
shortest
running
hours will start first. After
start time reaches set
duty time, the next genset
which has the shortest
running hours will start.
The gensets which has
the longest running
hours will stop first.
√
Х
Х