![Smartgen HPM6 Скачать руководство пользователя страница 109](http://html1.mh-extra.com/html/smartgen/hpm6/hpm6_user-manual_1297544109.webp)
HPM6 Power Management Controller User Manual
Page 109 of
146
No.
Name
Description
Auto
Mode
Semi-auto
Mode
Manual
Mode
Input
output from voltage control output port.
96.
Single Pulse
Voltage Drop
Input
Х
Х
√
97.
Shore Switch 0
Close
Feedback Input
Shore switch close feedback input.
√
√
Х
98.
Shore Switch 1
Close
Feedback Input
√
√
Х
99.
Shore Switch 2
Close
Feedback Input
√
√
Х
100.
Shore Switch 3
Close
Feedback Input
√
√
Х
101.
External
Reactive Adjust
Simulate adjust voltage/reactive power
input is active when the input port is active.
Controller
automatically
adjust
voltage/reactive power according to
configuration when the input port is
inactive.
√
√
Х
102~150 Reserved
Reserved
12.8
DIGITAL OUTPUT PORTS SETTING
Table 325 – Output Ports Setting
No.
Items
Range
Default
Description
Digital Output Ports
Digital Output Port 1
1
Contents Setting
Alarm/Function
(0-255)
Function
007
Crank output.
2
Active Type
(0-1)
0
0: Normally Open 1: Normally Close
Digital Output Port 2
3
Contents Setting
Alarm/Function
(0-255)
Function
008
Start output.
4
Active Type
(0-1)
0
0: Normally Open 1: Normally Close
Digital Output Port 3
5
Contents Setting
Alarm/Function
(0-255)
Function
001
Speed raise output.
6
Active Type
(0-1)
0
0: Normally Open 1: Normally Close
Digital Output Port 4