HPM6 Power Management Controller User Manual
Page 74 of
146
No.
Items
Range
Default
Description
max loading frequency, it will enter
into normal running.
9
Crank Disconnect Freq (0-200.0)%
85
To offer standards for detecting
crank disconnect frequency is
satisfied or not.
10
Phase Sequence Select (0-1)
0
0: L1-L2-L3
1: L1-L3-L2
11
Harmonic Display
(0-1)
0: Disable
0: Disable; 1: Enable
12
Volt.
Trans.(PT)
Action
(0-1)
0: Disable
1: Enable
0: Disable
Primary/secondary
voltage
of
voltage transformer can be set.
13
PT Primary (30-30000)V
100
14
PT
Secondary
(30-1000)V
100
15
Loss
of
Phase Set
Action
(0-1)
1: Enable
16
Auto ACK
(0-1)
0: Disable
17
Alarm
Self-lock
(0-1)
0: Disable
18
Delay Value (0.1-3600.0)s
5.0
19
Alarm Type (0-6)
1: Warning
20
Active
Range
(0-20)
6:
Gen
Normal
21
Reverse
Phase
Sequence
Action
(0-1)
1: Enable
22
Auto ACK
(0-1)
0: Disable
23
Alarm
Self-lock
(0-1)
0: Disable
24
Delay Value (0.1-3600.0)s
5.0
25
Alarm Type (0-6)
1: Warning
26
Active
Range
(0-20)
6:
Gen
Normal
27
VECTOR
SHIFT 1
Action
(0-1)
0: Disable
When controller detects gen vector
shift is greater than set value, it will
initiate alarm signal and alarm
information will be displayed on
LCD.
28
Auto ACK
(0-1)
0: Disable
29
Alarm
Self-lock
(0-1)
0: Disable
30
Threshold (0-60.0)°
6.0
31
Return
Value
(0-60.0)°
5.0
32
Delay Value (0.1-3600.0)s
0.1
33
Alarm Type (0-6)
1: Warning
34
Active
Range
(0-20)
6:
Gen
Normal
35
VECTOR
Action
(0-1)
0: Disable