No.
Item
Range
Default
Description
30
Alarm
Self-lock
(0-1)
0: Disable
31
Threshold
(0-200.0)%
120.0
32
Return Value (0-200.0)%
115.0
33
Delay Value
(0.1-3600.0)s
60.0
34
Alarm Type
(0-6)
1: Warning
35
Active Range (0-20)
0:
Always
Active
36
Under
Volt 1
Action
(0-1)
1: Enable
37
Auto ACK
(0-1)
0: Disable
38
Alarm
Self-lock
(0-1)
0: Disable
39
Threshold
(0-200.0)%
85.0
40
Return Value (0-200.0)%
90.0
41
Delay Value
(0.1-3600.0)s
60.0
42
Alarm Type
(0-6)
1: Warning
43
Active Range (0-20)
0:
Always
Active
44
Under
Volt 2
Action
(0-1)
0: Disable
45
Auto ACK
(0-1)
0: Disable
46
Alarm
Self-lock
(0-1)
0: Disable
47
Threshold
(0-200.0)%
85.0
48
Return Value (0-200.0)%
90.0
49
Delay Value
(0.1-3600.0)s
60.0
50
Alarm Type
(0-6)
1: Warning
51
Active Range (0-20)
0: Always
52
1#DIN
16
Action
(0-1)
0: Disable
When HPM6 input ports are
insufficient, expand external input
module 1 is used, if still not enough,
input module 2 is used.
53
Auto ACK
(0-1)
0: Disable
54
Alarm
Self-lock
(0-1)
0: Disable
55
Delay Value
(0.1-3600.0)s
5.0
56
Alarm Type
(0-6)
1: Warning
57
2#DIN
16
Action
(0-1)
0: Disable
58
Auto ACK
(0-1)
0: Disable
59
Alarm
Self-lock
(0-1)
0: Disable
60
Delay Value
(0.1-3600.0)s
5.0
61
Alarm Type
(0-6)
1: Warning
62
1#DO
UT16
Action
(0-1)
0: Disable
When HPM6 output ports are
insufficient, expand external output
module 1 is used, if still not enough,
63
Auto ACK
(0-1)
0: Disable
64
Alarm
(0-1)
0: Disable