HPM6 Power Management Controller User Manual
Page 85 of
146
No.
Items
Range
Default
Description
Close Delay
10: Before
Gen Close
Delay
11: Gen Load
Normal
12: Gen Close
Delay on Bus
13: No Gen
Close Delay
on Bus
14: Gen
Normal Delay
15: Other
Gens Close
Delay
16: Gen Load
Normal Delay
17-20:
Reserved
75.
Gen Current
2 Set
Action
(0-1)
1: Enable
76.
Auto ACK
(0-1)
0: Disable
77.
Alarm Self-lock
(0-1)
0: Disable
78.
Threshold
(0-200.0)%
110.0
79.
Return Value
(0-200.0)%
109.0
80.
Delay Value
(0.1-3600.0)s 60.0
81.
Alarm Type
(0-6)
2: Trip
82.
Active Range
(0-20)
0: Always
Active
83.
Gen Current
3 Set
Action
(0-1)
1: Enable
84.
Auto ACK
(0-1)
0: Disable
85.
Alarm Self-lock
(0-1)
0: Disable
86.
Threshold
(0-200.0)%
130.0
87.
Return Value
(0-200.0)%
129.0
88.
Delay Value
(0.1-3600.0)s 30.0
89.
Alarm Type
(0-6)
2: Trip
90.
Active Range
(0-20)
0: Always
Active
91.
Gen Current
4 Set
Action
(0-1)
1: Enable
92.
Auto ACK
(0-1)
0: Disable
93.
Alarm Self-lock
(0-1)
0: Disable
94.
Threshold
(0-200.0)%
150.0