HPM6 Power Management Controller User Manual
Page 130 of
146
No.
Item
Range
Default
Description
31
Max On-grid
Gensets
(0-16)
16
The maximum scheduling on-grid gensets on
the current bus.
32
Priority Active
(0-1)
0
If it is disabled, power management function
will not change bus genset start/stop status
due to priority change. It will only be active
when bus needs to schedule other gensets to
start.
33
Top Priority
(0-1)
1
When it is enabled, press top priority key, the
current genset will have the highest priority,
other gensets will sort again;
When it is disabled, only the current genset
has the highest priority, other genset priority
has no change.
34
System Mode
(0-1)
0
If it is enabled, all bus gensets controllers
mode will be changed by switching mode
(key or input port).
35
Duty Start Run
(0.1-100.0)h 5.0
When it is duty time start, genset with
smallest running time will start first, the next
genset with less running time will start when
start time reaches set duty time.
The running time here refers to the
accumulated running time of user A.
36
Bus Blackout
Starts
(0-16)
0
Started gensets in bus blackout.
37
Bus Blackout Start
Running Time
(0-3600)s
600
Continuous running time of started gensets
in bus blackout.
38
Short Close Times
(0-1)
0
Again close times when short trip is
detected.
39
Bus Blackout Mode (0-2)
0
0 No Change
1 Semi-auto Mode
2 Auto Mode
40
Inhibit Blackout
(0-1)
0
0: Disable; 1: Enable.
When it is enabled in auto mode, only one
genset on the bus takes load, other general
trip and stop alarm open except for
overspeed, overfrequency, emergency trip
and stop, overcurrent is inhibited. Fault
genset can open after other normal gensets
starting with load.
In manual mode, when only one genset on
the bus takes load, general trip, stop alarm
open and stop and manual open and stop are