HPM6 Power Management Controller User Manual
Page 71 of
146
No.
Items
Range
Default
Description
Bus
54
Under
Voltage 2
Set
Action
(0-1)
1: Enable
55
Auto ACK
(0-1)
0: Disable
56
Alarm
Self-lock
(0-1)
0: Disable
57
Threshold
(0-200.0)%
80.0
58
Return
Value
(0-200.0)%
81.0
59
Delay Value (0.1-3600.0)s
3.0
60
Alarm Type (0-6)
2: Trip
61
Active
Range
(0-20)
4:
Gen
Close on
Bus
62
Under
Voltage 3
Set
Action
(0-1)
0: Disable
63
Auto ACK
(0-1)
0: Disable
64
Alarm
Self-lock
(0-1)
0: Disable
65
Threshold
(0-200.0)%
70.0
66
Return
Value
(0-200.0)%
71.0
67
Delay Value (0.1-3600.0)s
2.0
68
Alarm Type (0-6)
2: Trip
69
Active
Range
(0-20)
4:
Gen
Close on
Bus
70
Over
Frequency 1
Set
Action
(0-1)
1: Enable
Setting value is bus rated frequency’s
percentage, return value and delay
value can be set according to actual
situations.
71
Auto ACK
(0-1)
0: Disable
72
Alarm
Self-lock
(0-1)
0: Disable
73
Threshold
(0-200.0)%
105.0
74
Return
Value
(0-200.0)%
104.0
75
Delay Value (0.1-3600.0)s
5.0
76
Alarm Type (0-6)
1: Warning
77
Active
Range
(0-20)
0: Always
Active
78
Over
Frequency 2
Set
Action
(0-1)
1: Enable
79
Auto ACK
(0-1)
0: Disable
80
Alarm
Self-lock
(0-1)
0: Disable
81
Threshold
(0-200.0)%
110.0
82
Return
(0-200.0)%
109.0