Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[units]
(units register)
Value range /
Setting options
Access
level
8878
Float / 4
Upper range
value standard
volume flow
Upper standard volume
flow value that is map‐
ped to the upper nomi‐
nal range boundary se‐
lected by Current mode
(8806). Applicable if
Process value (8802) =
27.
0.4 % • stna‐
dard volume
flow
[Sm
3
/h]
(7964)
-
Read /
write
8880
Float / 4
Lower range
value standard
volume flow
Lower standard volume
flow value that is map‐
ped to the lower nomi‐
nal range boundary se‐
lected by Current mode
(8806). Applicable if
Process value (8802) =
27.
0.0
[Sm
3
/h]
(7964)
-
Read /
write
10000
Float / 4
Upper range
value velocity
Upper velocity value
that is mapped to the
upper nominal range
boundary selected by
Current mode (8806).
Applicable if Process
value (8802) = 18, 19 or
31.
1.0
[m/s]
(8014 / 7648)
-
Read /
write
10002
Float / 4
Lower range
value velocity
Lower velocity value
that is mapped to the
lower nominal range
boundary selected by
Current mode (8806).
Applicable if Process
value (8802) = 18, 19 or
31.
0.0
[m/s]
(8014 / 7648)
-
Read /
write
10004
Float / 4
Upper range
value pressure
Upper process pres‐
sure value that is map‐
ped to the upper nomi‐
nal range boundary se‐
lected by Current mode
(8806). Applicable if
Process value (8802) =
20.
100000.0
[Pa]
(7548)
-
Read /
write
10006
Float / 4
Lower range
value pressure
Lower process pres‐
sure value that is map‐
ped to the lower nomi‐
nal range boundary se‐
lected by Current mode
(8806). Applicable if
Process value (8802) =
20.
0.0
[Pa]
(7548)
-
Read /
write
MODBUS commands
4.10 Modbus holding registers tables
FCT030 Modbus (From firmware 4.0)
Function Manual, 06/2018, A5E39931813-AB
83
Содержание SITRANS F Coriolis FCT030
Страница 6: ...Table of contents FCT030 Modbus From firmware 4 0 6 Function Manual 06 2018 A5E39931813 AB ...
Страница 16: ...Communication 2 4 Connecting FCT030 Modbus From firmware 4 0 16 Function Manual 06 2018 A5E39931813 AB ...
Страница 194: ...Definitions A 1 Definitions FCT030 Modbus From firmware 4 0 194 Function Manual 06 2018 A5E39931813 AB ...