Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
7593
Unsigned / 2
Recipe 4 Dec.
point volume
flow
Specify the selected
number of decimals for
volume flow
-
-
Read /
write
7594
Unsigned / 2
Recipe 4 Dec.
point corrected
volume flow
Specify the selected
number of decimals for
corrected volume flow
-
-
Read /
write
9715
Float / 4
Recipe 4 fixed
compensation
Mass flow
Fixed compensation
mass flow value that is
used to close the
valve(s) before the
measured amount val‐
ue has reached the tar‐
get amount
-
-
Read /
write
9717
Float / 4
Recipe 4 fixed
compensation
Volume flow
Fixed compensation
volume flow value that
is used to close the
valve(s) before the
measured amount val‐
ue has reached the tar‐
get amount
-
-
Read /
write
9719
Float / 4
Recipe 4 fixed
compensation
Corrected vol‐
ume flow
Fixed compensation
corrected volume flow
value that is used to
close the valve(s) be‐
fore the measured
amount value has
reached the target
amount
-
-
Read /
write
9791
Unsigned / 2
Recipe 4 com‐
pensation mode
Compensation algo‐
rithm, fixed or adaptive
compensation
0
0: fixed compensation
value is taken
1: On Target
2: Target plus
3: Target minus
Read /
write
9725
Float / 4
Recipe 4 over‐
run mass flow
value
When the amount
mass flow has reached
this value a dosing
overrun fault is raised.
Read /
write
9727
Float / 4
Recipe 4 over‐
run volume flow
value
When the amount vol‐
ume flow has reached
this value a dosing
overrun fault is raised.
Read /
write
9729
Float / 4
Recipe 4 over‐
run corrected
volume flow val‐
ue
When the amount cor‐
rected volume flow has
reached this value a
dosing overrun fault is
raised.
Read /
write
MODBUS commands
4.10 Modbus holding registers tables
FCT030 Modbus (From firmware 4.0)
162
Function Manual, 06/2018, A5E39931813-AB
Содержание SITRANS F Coriolis FCT030
Страница 6: ...Table of contents FCT030 Modbus From firmware 4 0 6 Function Manual 06 2018 A5E39931813 AB ...
Страница 16: ...Communication 2 4 Connecting FCT030 Modbus From firmware 4 0 16 Function Manual 06 2018 A5E39931813 AB ...
Страница 194: ...Definitions A 1 Definitions FCT030 Modbus From firmware 4 0 194 Function Manual 06 2018 A5E39931813 AB ...
Страница 198: ...Index FCT030 Modbus From firmware 4 0 198 Function Manual 06 2018 A5E39931813 AB ...