Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[units]
(units register)
Value range /
Setting options
Access
level
7705
Float / 4
Lower warning
limit
Falling below this
limit causes a warn‐
ing.
min. medium
temperature
[°C]
(7700)
min. medium temperature -
max. medium temperature
Read /
write
7707
Float / 4
Lower alarm
limit
Falling below this
limit causes an
alarm.
min. medium
temperature
[°C]
(7700)
min. medium temperature -
max. medium temperature
Read /
write
7712
Float / 4
Hysteresis
Hysteresis that af‐
fects the alarm and
warning limits.
0.0
[K]
0.0 - 200.0
Read /
write
Table 4-20
Medium temperature settings
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[units]
(units register)
Value range /
Setting options
Access
level
7715
Float / 4
Upper alarm
limit
Exceeding this limit
causes an alarm.
max. medium
temperature
[°C]
(7700)
min. medium temperature -
max. medium temperature
Read /
write
7717
Float / 4
Upper warning
limit
Exceeding this limit
causes a warning.
max. medium
temperature
[°C]
(7700)
min. medium temperature -
max. medium temperature
Read /
write
7719
Float / 4
Lower warning
limit
Falling below this
limit causes a warn‐
ing.
min. medium
temperature
[°C]
(7700)
min. medium temperature -
max. medium temperature
Read /
write
7721
Float / 4
Lower alarm
limit
Falling below this
limit causes an
alarm.
min. medium
temperature
[°C]
(7700)
min. medium temperature -
max. medium temperature
Read /
write
7723
Float / 4
Hysteresis
Hysteresis that af‐
fects the alarm and
warning limits.
0.0
[K]
0.0 - 200.0
Read /
write
Table 4-21
Fraction Flow Media A in Percent settings
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[units]
(units register)
Value range /
Setting options
Access
level
7802
Float / 4
Upper alarm
limit
Exceeding this limit
causes an alarm.
100
0 - 100
Read /
write
7804
Float / 4
Upper warning
limit
Exceeding this limit
causes a warning.
100
0 - 100
Read /
write
7806
Float / 4
Lower warning
limit
Falling below this
limit causes a warn‐
ing.
0
0 - 100
Read /
write
MODBUS commands
4.10 Modbus holding registers tables
FCT030 Modbus (From firmware 4.0)
Function Manual, 06/2018, A5E39931813-AB
71
Содержание SITRANS F Coriolis FCT030
Страница 6: ...Table of contents FCT030 Modbus From firmware 4 0 6 Function Manual 06 2018 A5E39931813 AB ...
Страница 16: ...Communication 2 4 Connecting FCT030 Modbus From firmware 4 0 16 Function Manual 06 2018 A5E39931813 AB ...
Страница 194: ...Definitions A 1 Definitions FCT030 Modbus From firmware 4 0 194 Function Manual 06 2018 A5E39931813 AB ...
Страница 198: ...Index FCT030 Modbus From firmware 4 0 198 Function Manual 06 2018 A5E39931813 AB ...