Par. No.
Name
Range
Default
Unit
P1000
Selection of frequency setpoint
0 - 53
5
--
Selects frequency setpoint source.
Possible settings:
0
No main setpoint
-
1
MOP setpoint
default value for the remote mode of C02 and
C10
2
Analog setpoint
default value for the remote mode of C03~C05
and C07~C09
3
Fixed frequency
default value for the remote mode of C06
5
Operator panel
default value for C01 and C11 and for the local
mode of C02~C10
12
Analog se MOP setpoint
can be used for the remote mode of C02~C10
and C11 if the function of DI reconfigured
13
Fixed fre MOP setpoint
can be used for the remote mode of C02~C10
and C11 if the function of DI reconfigured
21
MOP se Analog setpoint
can be used for the remote mode of C02~C10
and C11 if the function of DI reconfigured
23
Fixed fre Analog setpoint
can be used for the remote mode of C02~C10
and C11 if the function of DI reconfigured
25
operation panel + Analog setpoint
can be used for C11 if the function of DI
reconfigured
31
MOP se Fixed frequency
can be used for the remote mode of C02~C10
and C11 if the function of DI reconfigured
32
Analog se Fixed frequency
can be used for the remote mode of C02~C10
and C11 if the function of DI reconfigured
35
operation panel + Fixed frequency
can be used for C11 if the function of DI
reconfigured
52
Analog se operation panel
can be used for C11 if the function of DI
reconfigured
53
Fixed fre operation panel
can be used for C11 if the function of DI
reconfigured
Note:
Default value depends on connection macro selected. See Table 7-11 for details.
For users who are familiar with MM4 serial converters, the value from the operation panel (P1000 = 5) equals
to the USS on COM link of MM serial converters.
P1074
Disabling an additional setpoint
0.0 - 2036.F
0.0
-
Common settings:
P1074 = 722.2 => Digital input 3
Dependency:
Accessible only if P0701 - P0703 = 99 (enabling the use of 722.0 - 722.2)
Parameter list
SINAMICS V10
92
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)