Typical connection mode 8 (C08)
Description:
1. In LOC mode, motor start/stop, rotation direction and speed can be controlled via the
operator panel.
2. In REM mode, motor start/stop and rotation direction can be controlled via an external PLC
(NPN type) connected to DI1 and DI2, motor speed via an external signal source.
L1
L2
3 AC 400V
L3
PE
Fuse
Contactor
Connection macro: C08
RPM Meter
D/A U
AO
M
N
PE L1
L3
L2
M
3~
U
V
W
5
+24V
0V
6
7
DI1
DI2
8
DI3
9
Digital Input
1
DO1 DO1
2
Digital Output
SINAMICS V10 Inverter
13
+10V
0V
Analog Input/Analog Output
14
15
AI1- AI1+
AO1+
16
AO1-
17
18
O
N
+
F
W
D
C
o
mma
n
d
O
N
+R
EV
C
o
mma
n
d
D
C
b
ra
ki
n
g
(o
p
ti
o
n
a
l)
Sp
e
e
d
C
o
mma
n
d
N
220 AC Supply
L
PLC (NPN type outputs)
DIP-switches
AO
(mA)
AO
(V)
I
U
AI
(mA)
AI
(V)
I
U
P6V5 M
RS-485
Com A Com B
Operator Panel
Lit while inverter running or alarm
Dim while inverter fault
Factory defaut setting:
Inverter running: Lamp ON
Inverter in any other status: Lamp OFF
Figure 6-8
Typical connection mode 8 (C08)
The DIP-switch settings
DIP-switch (AO): Depends on the external signal source
DIP-switch (AI): Depends on the external signal source
Table 6-8
Select connection macro C08 with the operator panel after the wiring (please refer to
"Operation mode
②
- Connection macro selection", and then below parameter settings
will be automatically finished.)
Par. No. Parameter name
Range
Unit
Default
r0007
Selected connection macro and application macro
C0100 - C1105
- -
C08xx*
P0610
Motor I
2
t reaction
0 - 2
- -
2
P0701
Function of digital input 1
0 - 99
- -
1
P0702
Function of digital input 2
0 - 99
- -
2
P0703
Function of digital input 3
0 - 99
- -
0
P1000
Selection of frequency setpoint
0 - 53
- -
2
P0725
PNP/NPN digital inputs
0 - 1
- -
0
Commissioning
6.1 Typical connection modes
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)
51