See also
Application macros (Page 56)
6.2
Application macros
Application macros
This chapter describes six application macros available:
Table 6-12
Descriptions to application macro
Application
macro
Name
Description
Typical load
A00
1)
Out of box
-
-
A01
Simple fan/pump with
light starting load
Varying load with low starting torque
Simple fan/pump
A02
Heavy pump with heavy
starting load
Pumping load with high starting torque Sewage pump, mud pump, screw
pump, gear pump, etc.
A03
Conveyor load
Applications which require smooth
speed-transition
Conveyor
A04
High inertia load
Load inertia is relatively high, which
requires slow starting/stopping
Centrifuge, roller, industry washer, etc.
A05
High torque load with
heavy dead load
Starting torque of common constant-
torque machine is relatively high, which
requires slow starting/stopping
Extruder, injection molding machine,
stirring mill
1)
A00 - Out of box is the default application macro, i.e. the application macro will be reset to A00 when a new connection
macro is selected.
Parameters related to application macros
Par.
No.
Name
Range
Unit
Default value
A00
A01
A02
A04
A05
A03
P1120 Ramp-up time
0.00 - 300.00
s
10.00
20.00
20.00
10.00
90.00
20.00
P1121 Ramp-down time
0.00 - 300.00
s
10.00
20.00
20.00
10.00
120.00 20.00
P1130 Ramp-up initial rounding
time
0.00 - 40.00
s
0.00
0.00
0.00
0.00
0.00
0.00
P1131 Ramp-up final rounding
time
0.00 - 40.00
s
0.00
0.00
0.00
0.00
0.00
0.00
P1132 Ramp-down initial
rounding time
0.00 - 40.00
s
0.00
0.00
0.00
0.00
0.00
0.00
Commissioning
6.2 Application macros
SINAMICS V10
56
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)