Par. No.
Name
Range
Default
Unit
P0757
Value x1 of ADC scaling [V]
0.00 - 10.00
0.00
V
Parameters P0757 - P0760 configure the input scaling as shown in the diagram:
ASPmax
100 %
10 V
V
x
100%
%
P0760
P0758
P0757
P0759
P0761 = 0
ASPmin
4000 h
ASPmax
100 %
20 mA
V
x
100%
%
P0760
P0758
P0757
P0759
P0761 = 0
ASPmin
4000 h
Where:
● Analog setpoints represent a [%] of the nominalized frequency in P2000.
● Analog setpoints may be larger than 100 %.
● ASPmax represents highest analog setpoint (this may be at 10 V / 20 mA).
● ASPmin represents lowest analog setpoint (this may be at 0 V / 0 mA).
● Default values provide a scaling of 0 V / 0 mA = 0%, and 10 V / 20 mA = 100%.
Note:
● The value x2 of ADC scaling P0759 must be greater than the value x1 of ADC scaling P0757.
● If P2200 = 1, P0757 to P0760 can only be set for PI feedback scaling.
P0758
Value y1 of ADC scaling
-99999 - 99999
0.00
%
Sets value of Y1 in [%] as described in P0757 (ADC scaling).
P0759
Value x2 of ADC scaling [V]
0.00 - 10.00
10.00
V
Sets value of x2 as described in P0757 (ADC scaling).
Note:
The value x2 of ADC scaling P0759 must be greater than the value x1 of ADC scaling P0757.
P0760
Value y2 of ADC scaling
-99999 - 99999
100.00
%
Sets value of Y2 in [%] as described in P0757 (ADC scaling).
P0761
Width of ADC deadband [V]
0.00 - 10.00
0.00
V
Defines width of deadband on analog input.
Parameter list
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)