* "xx" means current application macro.
Typical connection mode 9 (C09)
Description:
1. In LOC mode, motor start/stop, rotation direction and speed can be controlled via the
operator panel.
2. In REM mode, motor start/stop can be controlled via an external signal source connected
to DI1, motor speed via an external potentiometer, motor rotation in JOG mode via external
signal sources connected to DI2 and DI3.
L1
L2
3 AC 400 V
L3
PE
Fuse
Contactor
Connection macro: C09
O
N
/O
F
F
C
o
mma
n
d
JO
G
F
o
rw
a
rd
C
o
mma
n
d
JO
G
R
e
ve
rse
C
o
mma
n
d
RPM Meter
Speed Reference
Potentiometer
N
PE L1
L3
L2
M
3~
U
V
W
5
+24V
0V
6
7
DI1
DI2
8
DI3
9
Digital Input
1
DO1 DO1
0 - 10 V DC
2
Digital Output
SINAMICS V10 Inverter
13
+10V
0V
14
15
AI1- AI1+
AO1+
16
AO1-
17
18
N
220 AC Supply
L
P6V5 M
RS-485
Com A Com B
Operator Panel
DIP-switches
AO
(mA)
AO
(V)
I
U
AI
(mA)
AI
(V)
I
U
Lit while inverter running or alarm
Dim while inverter fault
Factory defaut setting:
Inverter running: Lamp ON
Inverter in any other status: Lamp OFF
Analog Input/Analog Output
Figure 6-9
Typical connection mode 9 (C09)
The DIP-switch settings
DIP-switch (AO): Depends on external RPM Meter
DIP-switch (AI): Must be set to voltage (V) mode
Table 6-9
Select connection macro C09 with the operator panel after the wiring (please refer to
"Operation mode
②
- Connection macro selection", and then below parameter settings
will be automatically finished.)
Par. No. Parameter name
Range
Unit
Default
r0007
Selected connection macro and application macro
C0100 - C1105
- -
C09xx*
P0610
Motor I
2
t reaction
0 - 2
- -
2
P0701
Function of digital input 1
0 - 99
- -
1
P0702
Function of digital input 2
0 - 99
- -
10
Commissioning
6.1 Typical connection modes
SINAMICS V10
52
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)