Par. No. Parameter name
Range
Unit
Default
P0703
Function of digital input 3
0 - 99
- -
11
P1000
Selection of frequency setpoint
0 - 53
- -
2
P0725
PNP/NPN digital inputs
0 - 1
- -
1
* "xx" means current application macro.
Typical connection mode 10 (C10)
Description:
1. In LOC mode, motor start/stop, rotation direction and speed can be controlled via the
operator panel.
2. In REM mode, motor start/stop can be controlled via an external signal source connected
to DI1, motor MOP-up/MOP-down via external signal sources connected to DI2 and DI3,
feedback value via an external sensor connected to terminals AI1+ and AI1-.
L1
L2
3 AC 400 V
L3
PE
Fuse
Contactor
Connection macro: C10
O
N
/O
F
F
C
o
mma
n
d
RPM Meter
0 - 10 V DC or
0 - 20 mA DC
from Feedback Sensor
N
PE L1
L3
L2
M
3~
U
V
W
5
+24V
0V
6
7
DI1
DI2
8
DI3
9
Digital Input
1
DO1 DO1
2
Digital Output
SINAMICS V10 Inverter
13
+10V
0V
Analog Input/Analog Output
14
15
AI1- AI1+
AO1+
16
AO1-
17
18
N
220 AC Supply
L
DIP-switches
AO
(mA)
AO
(V)
I
U
AI
(mA)
AI
(V)
I
U
P6V5 M
RS-485
Com A Com B
Operator Panel
MO
P-u
p
C
o
mma
n
d
MO
P-d
o
w
n
C
o
mma
n
d
Lit while inverter running or alarm
Dim while inverter fault
Factory defaut setting:
Inverter running: Lamp ON
Inverter in any other status: Lamp OFF
Figure 6-10 Typical connection mode 10 (C10)
The DIP-switch settings in this application
DIP-switch (AO): Depends on the external signal source
DIP-switch (AI): Depends on the external signal source
Commissioning
6.1 Typical connection modes
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)
53