NOTICE
"P" of parameters in quick commissioning is followed by a ".", for example, P.0304 and P.
1080.
Motor parameters can only be set in "Operation mode ① - Quick motor data setting
(Page 66)", but in "Operation mode
⑤
- Acess all the parameters", all the motor parameters
except for P0305 are read-only.
Motor data
In SINCAMICS V10, the factory default motor parameter values are set based on SIEMENS
1LG0 4-pole AC motors. (See table below for default motor data settings of SIEMENS 1LG0
4-pole AC motors.) You can change the defaults against data shown on the rating plate of your
motor connected.
SIEMENS 1LG0 4-pole AC motors
Rated inverter
output power (kW)
Motor
frame
size
Motor Type
Rated speed
(rpm)
Rated motor
efficiency
(%)
Power
factor
Rated
current (A)
Rated
torque
(Nm)
0.55
80M
1LG0080-4AA..
1390
71.0
0.750
1.57
3.8
0.75
80M
1LG0083-4AA..
1380
73.0
0.760
2.05
5.2
1.1.
90S
1LG0090-4AA..
1390
76.2
0.760
2.89
7.6
1.50
90L
1LG0096-4AA..
1390
78.5
0.790
3.67
10.3
2.20
100L
1LG0106-4AA..
1410
81.0
0.800
5.16
14.9
3.00
100L
1LG0107-4AA..
1410
82.8
0.810
6.80
20.3
4.00
112M
1LG0113-4AA..
1435
84.5
0.820
8.80
26.6
5.50
132S
1LG0130-4AA..
1440
86.0
0.820
11.80
36.5
7.50
132M
1LG0133-4AA..
1440
87.2
0.840
15.60
49.7
11.00
160M
1LG0163-4AA..
1460
89.0
0.830
22.60
72.0
15.00
160L
1LG0166-4AA..
1460
90.0
0.840
30.10
98.1
18.50
180M
1LG0183-4AA..
1470
90.6
0.860
36.10
120.2
22.00
180L
1LG0186-4AA..
1470
91.4
0.860
42.50
143.0
Commissioning
6.4 Quick commissioning
SINAMICS V10
64
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)