Par. No. Parameter name
Range
Unit
Default
P1000
Selection of frequency setpoint
0 - 53
- -
2
P0725
PNP/NPN digital inputs
0 - 1
- -
1
* "xx" means current application macro.
Typical connection mode 5 (C05)
Description:
1. In LOC mode, motor start/stop, rotation direction and speed can be controlled via the
operator panel.
2. In REM mode, motor start/stop can be controlled via an external signal source connected
to DI2, motor speed via an external potentiometer.
3. LOC and REM mode switch-over is controlled via an external signal source connected to
DI1.
L1
L2
3 AC 400 V
L3
PE
Fuse
Contactor
Connection macro: C05
Au
to
RPM Meter
Speed Reference
Potentiometer
N
O
N
/O
F
F
C
o
mma
n
d
D
C
b
ra
ki
n
g
(o
p
ti
o
n
a
l)
Ma
n
u
a
l
L
o
ca
l/
R
e
mo
te
mo
d
e
se
le
ct
io
n
PE L1
L3
L2
M
3~
U
V
W
5
+24V
0V
6
7
DI1
DI2
8
DI3
9
Digital Input
1
DO1 DO1
0 - 10 V DC
2
Digital Output
SINAMICS V10 Inverter
13
+10V
0V
Analog Input/Analog Output
14
15
AI1- AI1+
AO1+
16
AO1-
17
18
N
220 AC Supply
L
DIP-switches
AO
(mA)
AO
(V)
I
U
AI
(mA)
AI
(V)
I
U
P6V5 M
RS-485
Com A Com B
Operator Panel
Lit while inverter running or alarm
Dim while inverter fault
Factory defaut setting:
Inverter running: Lamp ON
Inverter in any other status: Lamp OFF
Figure 6-5
Typical connection mode 5 (C05)
The DIP-switch settings in this application
DIP-switch (AO): Depends on external RPM Meter
DIP-switch (AI): Must be set to voltage (V) mode
Commissioning
6.1 Typical connection modes
SINAMICS V10
46
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)