OK
Press
Set the current control mode to LOCAL status
Change wrong parameter setting,
then wait till “F0003” reappears
SET
Long-press
If necessary, set the control mode to REMOTE status
SET
Short-press to clear the fault code.
(P0005-set default inverter status display)
(P0005-set default inverter status display)
(Fault-specific parameter)
. . .
Turn
(Fault code cleared)
OK
SET
SET
Figure 8-1
Acknowledging and clearing F0003 (example)
● Alternative 2: Re-power on the inverter
● Alternative 3: If a digital input terminal has been configured as the fault clearance terminal
via either one of the parameters P0701 to P0703, acknowledge and clear the fault via the
digital input terminal.
NOTICE
When multi-faults occur, the fault code is always displayed as x.Fxxx. For example:
"1.F002" = The first fault code F0002
"2.F011" = The second fault code F0011
To view the fault history, go to r0947.
Troubleshooting
SINAMICS V10
108
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)