Par. No.
Name
Range
Default
Unit
r0052
Actual status word 1
--
--
--
Displays first active status word of inverter (bit format) and can be used to diagnose inverter status.
Bit fields:
Bit00
Inverter ready
0
NO
1 YES
Bit01
Inverter ready to run
0
NO
1 YES
Bit02
Inverter running
0
NO
1 YES
Bit03
Inverter fault active
0
NO
1 YES
Bit04
OFF2 active
0
YES
1 NO
Bit05
OFF3 active
0
YES
1 NO
Bit06
ON inhibit active
0
NO
1 YES
Bit07
Inverter warning active
0
NO
1 YES
Bit08
Deviation setpoint / actual value
0
YES
1 NO
Bit09
PZD control
0
NO
1 YES
Bit10
Maximum frequency reached
0
NO
1 YES
Bit11
Warning: Motor current limit
0
YES
1 NO
Bit12
Motor holding brake active
0
NO
1 YES
Bit13
Motor overload
0
YES
1 NO
Bit14
Motor runs right
0
NO
1 YES
Bit15
Inverter overload
0
YES
1 NO
Note:
For the explanation of the 7-segment display of the bit-parameters (binary parameters), see topic "Operator
panel overview (Page 58)"
r0206
Rated inverter power
--
--
kW
Displays nominal rated motor power from inverter.
r0207[2]
Rated inverter current
--
--
A
Displays maximum continuous output current of inverter.
r0207[0] :
Rated inverter current
r0207[1] :
Rated motor current of a 4-pole 1LA7 AC motor.
Note:
Under this index 1, you can only view the rated motor current of a 4-pole 1LA7 AC motor. To
view the actual motor current, go to P0305.
r0208
Rated inverter voltage
--
--
V
Displays nominal AC supply voltage of inverter.
Value:
r0208 = 400 ( 400 V, tolerance: -15% - +15%)
r0209
Maximum inverter current
--
--
A
Displays maximum output current of inverter.
Dependency:
Parameter r0209 depends on the derating which is affected by pulse frequency P1800, ambient temperature
and altitude. The data of derating is given in the Operating Instructions.
Parameter list
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)
81