Parameters
10.2 Parameter list
SINAMICS V90, SIMOTICS S-1FL6
358
Operating Instructions, 04/2019, A5E36037884-007
Par. No.
Name
Min
Max
Factory
Setting
Unit Data
type
Effective
Can be
changed
p29003
Control mode
0
9
0
-
I16
RE
T
Description: Selection of control mode.
•
0: Position control with pulse train input (PTI)
•
1: Internal position control (IPos)
•
2: Speed control (S)
•
3: Torque control (T)
•
4: Control change mode: PTI/S
•
5: Control change mode: IPos/S
•
6: Control change mode: PTI/T
•
7: Control change mode: IPos/T
•
8: Control change mode: S/T
•
9: Fast position control with pulse train input (Fast PTI)
Note: The compound control mode can be controlled by the digital input signal C-MODE. When DI10 (C-
MODE) is 0, the first control mode of control change mode is selected; otherwise, the second one is selected.
p29004
RS485 address
1
31
1
-
U16
RE
T
Description: Configuration of the RS485 bus address. The RS485 bus is used to transfer current absolute
position of the servo drive to the controller/PLC.
Note: Changes only become effective after power on. The parameter isn't influenced by default function.
p29005
Braking resistor capacity
percentage alarm thresh-
old
1
100
100
%
Float
IM
T
Description: Alarm triggering threshold for the capacity of the internal braking resistor.
Alarm number: A52901
p29006
Line supply voltage
200
480
400/230 V
U16
IM
T
Description: Nominal Line supply voltage, effective value of line to line voltage. Drive can operate within -15%
to +10% error.
For V90 400 V variant, the value range is 380 V to 480 V, default value is 400 V.
For V90 200 V variant, the value range is 200 V to 240 V, default value is 230 V.
p29007
RS485 protocol
0
2
1
-
I16
RE
T
Description: Set the communication protocol for the field bus interface:
•
0: No protocol
•
1: USS
•
2: Modbus
Note: Changes only become effective after power on. The parameter isn't influenced by default function.
p29008
Modbus control source
1
2
2
-
I16
RE
T
Description: Select the Modbus control source:
•
1: Setpoint and control word from Modbus PZD
•
2: No control word
–
No setpoint and control word from Modbus PZD
Note: Changes only become effective after power on.
Содержание SIMOTICS S-1FL6
Страница 1: ...SINAMICS V90 SIMOTICS S 1FL6 ...
Страница 2: ......
Страница 87: ...Mounting 3 1 Mounting the drive SINAMICS V90 SIMOTICS S 1FL6 Operating Instructions 04 2019 A5E36037884 007 85 ...
Страница 89: ...Mounting 3 1 Mounting the drive SINAMICS V90 SIMOTICS S 1FL6 Operating Instructions 04 2019 A5E36037884 007 87 ...
Страница 342: ...Tuning 9 9 PI P switching SINAMICS V90 SIMOTICS S 1FL6 340 Operating Instructions 04 2019 A5E36037884 007 ...
Страница 384: ...Parameters 10 2 Parameter list SINAMICS V90 SIMOTICS S 1FL6 382 Operating Instructions 04 2019 A5E36037884 007 ...
Страница 432: ......