Commissioning and optimization (software)
7.3 Commissioning and optimization of the drive application
ET 200pro FC
Operating Instructions, 07/2016, A5E01100763B AC
99
JOG frequency
Parameter
Description
Setting
P1057 = 1
JOG Enable
P1057 = 0 JOG-function disabled
P1057 = 1 JOG-function enabled (default)
P1058 = 5
JOG frequency right
Frequency in Hz when the motor is being jogged in the clockwise direction.
P1059 = 5
JOG frequency left
Frequency in Hz when the motor is being jogged in the counter-clockwise direction.
P1060 = 45
JOG ramp-up time
Ramp-up time in seconds from 0 to the maxi-
mum frequency (P1082). The JOG ramp-up is
limited by P1058 or P1059.
P1061 = 50
JOG ramp-down time
Ramp-down time in seconds from the maximum
frequency (P1082) to 0.
Additional setpoints
Parameters
Description (parameter name and factory setting in bold)
Setting
P1074 = 1.0
BI: Disable additional setpoint
P1075 = 775
CI: Additional setpoint
Specifies the source of the additional setpoint, which is added to the main setpoint.
P1076 = 1.0
CI: Additional setpoint scaling
Defines the source for scaling the additional setpoint.
General settings:
1: Scaling 1.0 (100%)
755: Analog input setpoint
1024: Fixed frequency setpoint
1050: MOP setpoint
Skip Frequency
Parameter
Description
Setting
P1091 = 7.5
Skip frequency 1 (entered in Hz)
Avoids mechanical resonance effects and suppresses (skips)
frequencies in the range around the skip frequency ± P1101
(skip frequency bandwidth).
P1092 = 0.0
Skip frequency 2
P1093 = 0.0
Skip frequency 3
P1094 = 0.0
Skip frequency 4
P1101 = 1.0
Skip frequency bandwidth (entered in Hz)
Содержание Simatic ET 200pro FC
Страница 1: ......
Страница 2: ......
Страница 12: ...Table of contents ET 200pro FC 12 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 158: ...Technical data 10 2 General ambient conditions ET 200pro FC 158 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 180: ...Appendix A 3 Standards ET 200pro FC 180 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 190: ...List of abbreviations acronyms B 1 Abbreviations ET 200pro FC 190 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 192: ...Glossary ET 200pro FC 192 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 195: ......
Страница 196: ......