Series commissioning and operation
8.2 Series commissioning and replacement of the frequency converter
ET 200pro FC
140
Operating Instructions, 07/2016, A5E01100763B AC
8.2
Series commissioning and replacement of the frequency converter
8.2.1
Application ID
The application ID is an important parameter for frequency converter standard
commissioning and replacement. It is specified in HW Config when the frequency converter
is configured (see Planning/Configuring) and saved in the PLC.
The application ID is designed to uniquely identify the frequency converter's parameter
assignment and to prevent frequency converters being swapped incorrectly.
Saving the application ID in the frequency converter
The very first time a connection is established between the PLC and frequency converter,
the application ID is accepted into the frequency converter and saved so that it is powerfail-
proof.
The frequency converter's application ID is also transferred and saved when the frequency
converter parameters are uploaded to an MMC or in STARTER.
Application ID during standard commissioning or replacement
When the frequency converter is replaced or after it has been parameterized by means of a
parameter download, the frequency converter receives the application ID from the PLC and
compares this value with the one saved in the frequency converter. If both values are
identical, the frequency converter is ready to run. If the values differ, the frequency converter
outputs fault F00395. In this case, you must check why the application IDs do not match.
Options for changing the application ID
There are two options for changing the application ID in the frequency converter:
●
Rejection of the parameter download
●
Acceptance of the parameter download
See "Fault codes during upload and download".
The application ID can, of course, be changed in the PLC too. Once the PLC has been
restarted, the modified application ID is transferred to the frequency converter.
Содержание Simatic ET 200pro FC
Страница 1: ......
Страница 2: ......
Страница 12: ...Table of contents ET 200pro FC 12 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 158: ...Technical data 10 2 General ambient conditions ET 200pro FC 158 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 180: ...Appendix A 3 Standards ET 200pro FC 180 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 190: ...List of abbreviations acronyms B 1 Abbreviations ET 200pro FC 190 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 192: ...Glossary ET 200pro FC 192 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 195: ......
Страница 196: ......