Commissioning (hardware)
6.2 Creating a drive configuration with STARTER
ET 200pro FC
Operating Instructions, 07/2016, A5E01100763B AC
87
6.2
Creating a drive configuration with STARTER
Procedure
●
Connect STARTER to the to the RS232 interface of the frequency converter.
●
Create a drive configuration and check the motor data.
Checking the motor terminal box (IEC/NEMA motor)
For commissioning to be successful, it is important that the interconnection in the motor
terminal box (see image below) corresponds to the entry for the rated motor voltage
(P0304)/rated motor current (P0305).
IEC motor
Delta connection
Star circuit configuration
e.g.: Voltage of 230 V (delta connection)/400 V (star connection)
NEMA motor
Voltage
U
V
W
Connected to one another
Circuit
Low
T
1
-T
7
T
2
-T
8
T
3
-T
9
T
4
-T
5
-T
6
Y Y
High
T
1
T
2
T
3
T
1
-T
7
T
2
-T
8
T
3
-T
9
Y
Содержание Simatic ET 200pro FC
Страница 1: ......
Страница 2: ......
Страница 12: ...Table of contents ET 200pro FC 12 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 158: ...Technical data 10 2 General ambient conditions ET 200pro FC 158 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 180: ...Appendix A 3 Standards ET 200pro FC 180 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 190: ...List of abbreviations acronyms B 1 Abbreviations ET 200pro FC 190 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 192: ...Glossary ET 200pro FC 192 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 195: ......
Страница 196: ......