Motor cable
Motor cables up to 10 m long are available under the following order designation:
●
6ES7194-1LA01-0AA0 (1.5 m)
●
6ES7194-1LB01-0AA0 (3.0 m)
●
6ES7194-1LC01-0AA0 (5.0 m)
●
6ES7194-1LD01-0AA0 (10.0 m).
Longer lengths up to 15 m can be obtained from our service providers.
Note
A metallic connector housing must be used for connecting.
The shield of the motor cable must be connected through a large area of the motor
enclosure (for EMC reasons).
Power transfer
The power jumper connector is used to loop-through the main power from one frequency
converter/motor starter to the next frequency converter/motor starter.
The table below shows the assignment of the contacts:
Table 4- 8
Power jumper connectors
Male (pin)
Female (socket) Assignment
1
1
Phase L1
2
2
Phase L2
3
3
Phase L3
4
4
Not assigned