Commissioning and optimization (software)
7.4 Commissioning of communication between the S7 CPU and the frequency converter
ET 200pro FC
114
Operating Instructions, 07/2016, A5E01100763B AC
Table 7- 13 Description of the fields for parameter requests
Field
Data type
Values Remark
Request ID
Unsigned 8
0x01
0x02
0x81
0x82
Read request (+)
Write request (+)
Read request (–)
Write request (–)
Request positive,
status ok
Request negative,
error state
Mirrors the request ID and indicates whether the execution of the request has
been positive or negative. Negative means: part of the - or the entire request
cannot be executed. The error values are transferred in place of the values for
every sub-response.
Drive object ID
See the table above
Qty Parameters
See the table above
Format
See the table above
Qty Values
See the table above
Values
See the table above
Error values
Unsigned 16
0x0000 … 0x00FF Meaning of the error values: See
the next table
The error values in the event of a negative response. A zero byte is appended if
the values result in an odd number of bytes. This ensures integrity of the word
structure in the telegram.
Note
The DRIVE-ES SIMATIC block package provides function blocks within the standard block
libraries for writing/reading parameters, including a few examples.
Error values in parameter responses
Table 7- 14 Error values in parameter responses
Error
value
Meaning
Remark
Additional
inf.
0x00
Invalid parameter number
Access to a non-existent parameter.
–
0x01
Parameter value cannot be modi-
fied.
Attempt to modify a read-only parame-
ter.
Subindex
0x02
Low or high limit exceeded
Attempted modification with value
outside limits.
Subindex
0x03
Invalid subindex
Access to non-existing subindex.
Subindex
0x04
No field
Access with subindex to non-indexed
parameter.
–
0x05
Incorrect data type
Attempt to modify with a value which is
incompatible with the data type of the
parameter.
–
Содержание Simatic ET 200pro FC
Страница 1: ......
Страница 2: ......
Страница 12: ...Table of contents ET 200pro FC 12 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 158: ...Technical data 10 2 General ambient conditions ET 200pro FC 158 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 180: ...Appendix A 3 Standards ET 200pro FC 180 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 190: ...List of abbreviations acronyms B 1 Abbreviations ET 200pro FC 190 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 192: ...Glossary ET 200pro FC 192 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 195: ......
Страница 196: ......