
Commissioning and optimization (software)
7.3 Commissioning and optimization of the drive application
ET 200pro FC
Operating Instructions, 07/2016, A5E01100763B AC
101
Parameters which must be set before ending the application settings
The following parameters must be configured for every application.
Parameters
Description (parameter name and factory setting (if non-variable) in bold print)
Setting
P1800 = 4
Pulse frequency (kHz)
The pulse frequency can be changed in steps of 2 kHz. The range extends from 2 kHz to 16
kHz. The full output current of the converter at 55 °C is 4 kHz.
The highest output frequency is limited by the pulse frequency. With a pulse frequency of 2
kHz, operation up to 133 Hz is possible. If a higher output frequency is required, the pulse
frequency should also be increased (10 kHz pulse frequency - maximum output frequency of
650 Hz).
If no low-noise operation is required, then the converter losses and the high-frequency inter-
ference transmitted by the converter can be reduced by selecting a lower pulse frequency.
P2000 = 50
Reference frequency (Hz)
The reference frequency in Hertz corresponds to a value of 100 %.
This setting should be changed if a maximum frequency greater than 50 Hz is required.
Comments: This scaling has an effect on the maximum frequency of the analog setpoints.
Fixed frequencies and standardization processes of the motor potentiometer are related to
100 %.
P2001 = 1000 Reference voltage (V)
The reference voltage in Volt (output voltage) corresponds to a value of 100 %.
Comments: This setting should only be changed if the power must be output with a different
scaling.
P2002 = ?
Reference current (A)
The reference current in Ampere (output current ) corresponds to a value of 100 %. The
factory setting equals 200 % of the rated motor current (P0305).
Comments: This setting should only be changed if the current must be output with a different
scaling.
P2003 = ?
Reference torque (Nm)
The reference torque in Newton meter corresponds to a value of 100 %. The factory setting
equals 200 % of the rated motor torque which is determined from the motor data for a con-
stant motor torque.
Comments: This setting should only be changed if the torque must be output with a different
scaling.
P2004 = ?
Reference power (kW or hp)
The reference power in kW or hp corresponds to a value of 100 %. The factory setting is
200 % of the rated motor torque at constant motor torque.
This setting should only be changed if the power must be output with a different scaling.
Ending the application settings
Parameters
Description (parameter name and factory setting (if non-variable) in bold print)
Setting
P0971 = 1
Adopting data from RAM into EEPROM
0: Inhibited
1: All parameter changes are transferred from RAM into EEPROM, i.e. the data are not lost if
there is a power failure.
Содержание Simatic ET 200pro FC
Страница 1: ......
Страница 2: ......
Страница 12: ...Table of contents ET 200pro FC 12 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 158: ...Technical data 10 2 General ambient conditions ET 200pro FC 158 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 180: ...Appendix A 3 Standards ET 200pro FC 180 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 190: ...List of abbreviations acronyms B 1 Abbreviations ET 200pro FC 190 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 192: ...Glossary ET 200pro FC 192 Operating Instructions 07 2016 A5E01100763B AC ...
Страница 195: ......
Страница 196: ......