data was saved to flash. Once the I/O extension box is available, the Inspector will read the
inputs of the box, and select the corresponding reference object.
2.4.2
Connection to the I/O extension box lost during operation
If the connection to the I/O extension box is lost during operation, the last status of the inputs
on the box will be used until the connection is re-established.
2.4.3
Object selection with I/O extension box
The status of the inputs on the I/O extension box is checked in the end of each inspection
cycle. If the Inspector is configured to use external image trig, the status of the external inputs
will only be checked when an image trig signal has been received.
2.4.4
Timing issues
The digital outputs on the I/O extension box shall be read at minimum delay time as displayed
in the
SOPAS Engineering Tool (ET)
application.
2.4.5
Use of the digital outputs for logic
The digital outputs on the I/O extension box are not guaranteed to be jitter-free. It is not re-
commended to use these outputs for direct control of other devices. The I/O extension box
shall be connected to a PLC for process control.
2.4.6
Change of Modules in the I/O extension box
The Inspector PIM60 supports I/O extension box configurations with up to 16 digital outputs
and 5 digital inputs (The standard configuration of the I/O extension box contains 8 digital
outputs and 4 digital inputs.). The configuration of an I/O extension box can be changed by
adding/removing I/O modules to/from the I/O extension box. I/O modules are available as
an accessory from SICK. For details about Accessories Ordering information see the Operating
Instructions for Inspector PIM60.
Perform the following steps to connect and use more I/O modules:
1. Close the
SOPAS Engineering Tool (ET)
application.
2. Disconnect the power from the I/O extension box.
3. Connect the additional I/O modules (inputs and/or outputs) to the I/O extension box.
Please refer to the manual delivered with the I/O extension box for details.
4. Re-connect the power to the I/O extension box.
5. Re-start the
SOPAS Engineering Tool (ET)
application.
The additional digital outputs are now be available in the
SOPASEngineeringTool(ET)
application.
2.5
Troubleshooting
2.5.1
The I/O LED flashes 10 times
If the power to the I/O extension box has been disconnected for a longer period of time, the
internal clock in the box will be reset. The I/O LED on the box will then flash 10 times in red.
This is not a serious error, and the I/O extension box can still be used together with the In-
spector without any problems.
2.5.2
No contact with the I/O extension box
Ensure that the network card on the PC has the same network address, for instance
192.168.1, as the I/O extension box. The host part of the IP address (that is the last number
in the IP address) must not be the same as for the I/O extension box or the Inspector.
There are two tools available in Windows to check the network connection and the IP settings:
•
Ping
. Open the command prompt, and type
ping
followed by the IP address of the I/O exten-
sion box. If the I/O extension box is available the following text will be displayed:
Reply from
x.x.x.x
(where x.x.x.x is the IP address of the I/O extension box). If the I/O extension box
11
©SICK AG • Identification & Measuring • www.sick.com • All rights reserved
Subject to change without notice
8015726/ZPP7/2018-
09
Interfaces
I/O extension box
Reference Manual
Inspector PIM