Operating Instructions – MOVIAXIS® MX Multi-Axis Servo Inverter
6
Operating displays and errors of MXA axis module
Operation
Table of errors
A "P" in the column "Error response" indicates that the response is programmable. The
factory set error response appears in the "Error response" column.
NOTES
Errors or sub-error codes, which are not included in the following list, can be displayed
within the framework of displayed error codes. In this case, contact SEW-EURO-
DRIVE.
Error
code
Error message Sub
error
code
Possible reason for error
Error response
(P = programma-
ble,
D = default
response)
Final error
status /
Reset type
Save
as
History
Message
binary out-
puts (valid
for default
response)
00
No error (this dis-
play is actually
an operation dis-
play -> see oper-
ation displays)
---
---
---
---
Ready = 1
(depending
on system
status)
Malfunction
= 1
01
Error "Overcur-
rent“
•
Short-circuit output
•
Motor too large
•
Defective output stage
Output stage
inhibit
System is
waiting
Warm start
Yes
Ready = 1
Malfunction
= 0
02
Error "UCE moni-
toring“
The error is an additional kind of
overcurrent, measured at the collec-
tor-emitter voltage of the output
stage. The possible reason behind
this error is identical to error 01. The
distinction is important for internal
purposes only.
Output stage
inhibit
System is
waiting
Warm start
Yes
Ready = 1
Malfunction
= 0
03
Error "Ground
fault“
Ground fault
•
in the motor lead
•
in the inverter
•
in the motor
Output stage
inhibit
System is
blocked
System restart
Yes
Ready = 0
Malfunction
= 0
04
Error "Brake
chopper“
Error message by SM via signal bus.
•
Too much regenerative power
•
Braking resistor circuit interrupted
•
Short circuit in the braking resis-
tor circuit
•
Brake resistor has too high resis-
tance
•
Brake chopper defective
Output stage
inhibit
System is
waiting
Warm start
Yes
Ready = 1
Malfunction
= 0
05
Error "Timeout
signaling bus”
The connection between supply mod-
ule and axis module via signaling bus
has been interrupted
Output stage
inhibit
System is
blocked
System restart
Yes
Ready = 0
Malfunction
= 0
01
Connection to signaling bus inter-
rupted
02
Timeout flag signaling bus cannot be
reset
06
Error "Mains
phase failure“
Error message by SM via signal bus.
It was detected that a mains phase is
missing.
Display only (D),
(P)
---------
Yes
Ready = 0
Malfunction
= 0
07
Error "U DC link“
Error message by SM via signaling
bus when DC link voltage is too high
Output stage
inhibit
System is
waiting
Warm start
Yes
Ready = 1
Malfunction
= 0