4
UL compliant installation
Installation
• The maximum permitted value of the input fuse is:
• Only use melting fuses as input fuses.
• If you use cable cross sections that are dimensioned for a smaller current than the
rated current of the unit, make sure that the fuse is dimensioned for the used cable
cross section.
• For information on selecting cable cross sections, refer to the project planning man-
ual.
• Comply with the country-specific installation regulations in addition to the above
notes.
• The plug-in connections of the 24 V supply are limited to 10 A.
• Option cards that are supplied via the 0 V and 24 V terminals at the front must be
protected individually or in groups by 4 A melting fuses to UL 248.
MXP power supply module
10 kW
25 kW
50 kW
75 kW
Input fuse
20 A
40 A
80 A
125 A
NOTES
UL certification does not apply to operation in voltage supply systems without earthed
star point (IT systems).
STOP
We recommend protection of the braking resistor with a thermal overload relay to im-
plement an UL approved application design.