Operating Instructions – MOVIAXIS® MX Multi-Axis Servo Inverter
5
MOVIAXIS® startup - Single-motor operation
Startup
Input data
Description
Motor
Enter the motor type without further information, such as gear unit, encoder,
brake or motor protection. For example:
•
Nameplate with gear unit PSF311RCM71S /BR /RH1M /SB51
→
motor
type CM71S;
•
Nameplate without gear unit CFM90M /BR /RH1M /SB51
→
motor type
CM90M.
Rated voltage
The rated motor voltage is the maximum voltage that the motor winding can
handle. The rated motor voltage refers to the rated mains voltage. For synchro-
nous motors, the value is indicated as U
max
on the nameplate.
Rated motor speed
The rated motor speed corresponds to the speed class on the nameplate.
Rated power supply
voltage
Enter the rated supply voltage, e. g. 400 V
Temperature sensor type
"Temperature sensor type" of the motor on the nameplate specifies which sen-
sor is used for implementing the motor protection:
•
No sensor;
•
TH Thermostat (bimetallic switch);
•
TF Thermistor sensor (PTC thermistor);
•
KTY thermistor for detection of motor temperature.
The KTY setting means the thermal motor model is activated in MOVIAXIS with
SEW motors. The thermal motor model protects the motor thermally together
with the KTY temperature sensor.
If the motor with KTY is a non-SEW motor, an I
2
t model is started if the XML file
of the non-SEW motor contains thermal data. The KTY only provides an initial
value. Afterwards, the calculation model is responsible for motor protection.
If the motor with KTY is a non-SEW motor and the XML file of the non-SEW
motor does not contain any thermal data, then a KTY limit temperature shut-
down is activated.
Response
Here you can set the shutdown response of the MOVIAXIS
®
MX multi-axis
servo drive in case of a motor overtemperature. The following settings are avail-
able:
•
No response
- Motor overtemperature is ignored.
•
Display only
- the error is only displayed in the 7-segment display; the axis
keeps on running.
•
Output stage inhibit / pending
- The axis switches to FCB controller inhibit
(motor coasts to a stop). The axis performs a "warm start" following a
"reset" (see chapter Operating Mode Display in the operating instructions).
The reset time is reduced to a minimum because there is no booting
involved.
•
Emergency stop / pending
- The axis decelerates using the emergency
stop ramp. The axis performs a "warm start" following a "reset" (see chapter
Operating Mode Display in the operating instructions). The reset time is
reduced to a minimum because there is no booting involved.
•
Stop at application limits / pending
- The axis decelerates using the
application ramp. The axis performs a "warm start" following a "reset" (see
chapter Operating Mode Display in the operating instructions). The reset
time is reduced to a minimum because there is no booting involved.
•
Stop at system limits / pending
- The axis decelerates using the system
ramp. The axis performs a "warm start" following a "reset" (see chapter
Operating Mode Display in the operating instructions or system manual).
The reset time is reduced to a minimum because there is no booting
involved.
Forced cooling fan
Use this field to enter whether the motor is equipped with a forced cooling fan.
The entered value will be used for the thermal motor model for motor protection.
Brake
Use this field to enter whether the motor is equipped with a brake. This will acti-
vate the brake function.
0
0
I