SP LINK | Configuration Settings
52
|
Doc #OI0005 Rev26 2020
If there is an automatic generator permanently connected to
the system the
Generator Controlle
r setting should be set to
Enabled. This is highly recommended for OFF Grid systems
If there is no automatic generator connected it should be
Disabled.
The
Auto Start Available
control allows 2 states. Follow Input
allows you to switch the generator availability on and off with
an input signal (normally 12 volts from the generator). This
ensures that the SP PRO will not try to start the generator if it
has become unavailable, e.g. starter battery flat or generator
maintenance is being performed. Assume Always allows the
inverter to operate as if the generator is always available.
Minimum Runtime
determines the shortest time the generator will run. This is
to ensure the generator wont start and stop too frequently.
The
Pre-synchronised warm Up Time
is the length of time, after the
generator starts, before the generator is connected (Transferred) to any load.
This is then followed by the
Warm Up Time
,
the length of time, after the
Pre-
synchronised warm Up Time
, before a charging sequence starts. Once
synchronised, the AC Load is transferred to the generator during the
Warm
Up Time
. The staged warm up sequence allows the generator to circulate
the oil within the motor thoroughly and to allow the motor to reach operating
temperature before being heavily loaded by the charger.
Cool Down Time
disconnects the load from a generator for a period of time
before shutdown to allow turbochargers to cool down before switching off. The
Cool Down Time
is overridden if generator is stopped using front panel push
button.
Generator Lock Out
provides a “quiet time” when the generator will not run
unless the batteries get to a dangerously low level as set in the Generator
Lockout Override (“Generator Auto start” tab). This setting is generally used for
overnight operation.
Generator Control Settings
The last tab in the AC Source section is the Generator Controller Settings
Содержание SP PRO 2i Series
Страница 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Страница 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Страница 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Страница 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...